Operating options Flowphant T DTT31, DTT35
20 Endress+Hauser
6.2.2 Navigating the Calibration (CAL) function group
Variable limits for HIF (Learn High Flow) or LOWF (Learn Low Flow) can be set with the
'Learn Function'.
HIF setting (Learn High Flow): Enter any flow rate from 70 to 100 % of the maximum value
in the process. The device then uses this value to automatically calculate the corresponding
100 % value.
LOWF setting (Learn Low Flow): Enter any flow rate from 0 to 20 % of the maximum value
in the process. The device then uses this value to automatically calculate the corresponding
0 % value.
B
OUT
C
E
E
CAL
HIF
RUN
LOWF
> 2 s
> 60 s
~ 10 s
WAIT
OK W432
E
80%
0%
1.
2.
3.
4.
5.
6.
7.
A0010787
 11 Navigating the 'Learn' function taking the example of the Calibration (CAL) function group
B Function selection
C Selection of settings
1. Select the "HIF" (Learn High Flow) or "LOWF" (Learn Low Flow) function with the E key.
2. Select the "RUN" function with the + key; the Learn function is initialized.
3. Select the flow rate with the + key; press for longer than 2 s.
4. If "HIF" (Learn High Flow) is set, the upper flow rate (70 to 100 %) is selected. Enter the
current relative flow rate in increments of 1 % with the + or - key (factory setting 80 %).
5. If "LOWF" (Learn Low Flow) is set, the lower flow rate (0 to 20 %) is selected. Enter the
current relative flow rate in increments of 1 % with the + or - key (factory setting 0%).
6. Select the "WAIT" function with the E key.
7. Accept ('learn') the current measured value after approx. 10 s- "OK" appears on the
display.