Gammapilot IECEx BVS 12.0080 X / XA00617F-A
Endress+Hauser 5
Instructions:
Ex d joints
Specification according to IEC/EN 60079-1:2007, Chapter 5.1
If required or if doubt: ask manufacturer for specifications.
Gammapilot with FEG24
Safety instructions:
Zone 1
Connect the device using suitable cable and wire entries or using piping systems of protection type
"Pressure-tight Enclosure d".
Close unused entry glands with approved (Ex d) sealing plugs.
The plastic sealing plug is used only as transport protection.
Transmitter housing: Do not open in a potentially explosive atmosphere.
During operation, the cover must be screwed all the way in and the cover's safety catch must be fastened.
Replace sealing plugs only with identical parts.
Lay connecting cable to the transmitter and secure.
The instrinsically safe signal circuit to the sensor is galvanically isolated from other circuits up to a peak value
of the nominal voltage of 375 V.
Safety instructions:
Zone 21
Connect the device using suitable cable and wire entries or using piping systems.
Only use suitable cable glands for Zone 21 with degree of protection IP68, which are suitable for an ambient
temperature of at least –40 °C...+70 °C.
Close unused entry glands with approved sealing plugs.
The plastic sealing plug is used only as transport protection.
Lay connecting cable to the transmitter and secure.
Transmitter housing: Do not open in a potentially explosive dust atmosphere.
Replace cable glands and sealing plugs only with identical parts.
The instrinsically safe signal circuit to the sensor is galvanically isolated from other circuits up to a peak value
of the nominal voltage of 375 V.
Gammapilot with FEG25
Safety instructions:
Zone 1, Zone 21
The pertinent guidelines must be observed when intrinsically safe circuits are connected together acc.
EN 60079-14 (Proof of Intrinsic Safety).
The intrinsically safe input power circuit of the device is isolated from ground potential and has a dielectric
strength of at least 500 V
rms
with respect to it.
The intrinsically safe signal circuit of the sensor is isolated from ground potential and has a dielectric strength
of at least 500 V
rms
with respect to it.
When the device is connected to an intrinsically safe circuit Ex ib, the level of protection changes to Ex ib.
When the device is connected to an intrinsically safe circuit Ex ic, the level of protection changes to Ex ic.
Do not operate intrinsically safe circuits Ex ic in zone 1 or zone 21.
Safety instructions:
Zone 21, Zone 22
For service operations, the transmitter housing may be opened under voltage for a short time.
If the terminal compartment is opened make sure that no dust may deposit.
After configuration close the cover according to good professional practice.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Gammapilot FTG20 and is the answer not in the manual?

Endress+Hauser Gammapilot FTG20 Specifications

General IconGeneral
BrandEndress+Hauser
ModelGammapilot FTG20
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals