Levelflex FMP51 Modbus
Endress+Hauser 31
Nozzle mounting
£150 (6)
H
ø 150 (6)£
A0015122
H Length of the center rod or the rigid part of the rope probe
Permissible nozzle diameter: ≤ 150 mm (6 in).
For larger diameters the near range measuring capability may be reduced.
For nozzles ≥ DN300: →  33.
Permissible nozzle height
5)
: ≤ 150 mm (6 in).
For a larger height the near range measuring capability may be reduced.
Larger nozzle heights may be possible in special cases (see sections "Center rod" ).
The end of the nozzle should be flush with the tank ceiling in order to avoid ringing effects.
With thermally insulated vessels the nozzle should also be insulated in order to prevent
condensate formation.
5) Larger nozzle heights on request