Electrical connection Levelflex FMP51 Modbus
22 Endress+Hauser
4. Remove the cable sheath.
5. Strip the cable ends 10 mm (0.4 in). In the case of stranded cables, also fit ferrules.
6. Firmly tighten the cable glands.
7.
A0035426
Connect the cable according to the terminal assignment → 18.
8. If using shielded cables: Connect the cable shield to the ground terminal.
9. Fit the cover of the connection compartment back on.
10. If present, turn the cover lock so that it is located over the edge of the cover and then
tighten.
6.2.1 Plug-in spring-force terminals
The electrical connection of device versions without an integrated overvoltage protection is
established at plug-in spring-force terminals. Rigid conductors or flexible conductors with
ferrules can be inserted directly into the terminal without using the lever, and create a contact
automatically.