Levelflex FMP51 Modbus Commissioning
Endress+Hauser 29
8.3 Device configuration
8.3.1 Configuring level measurement
A0011360
7 Configuration parameters for level measurement in liquids
LN = Probe length R = Reference point of measurement
D = Distance E = Empty calibration (= zero point)
L = Level F = Full calibration (= span)
1. Setup → Device tag
Enter device tag.
2. Setup → Distance unit
Select the length unit.
3.
Setup→Operating mode
1)
Select Level option.
4. Setup → Tank type
Select tank type.
5. Setup → Tube diameter (only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
1) Only available in devices with the "Interface measurement" application package