Commissioning Levelflex FMP51 Modbus
30 Endress+Hauser
6. Setup → Medium group
Specify the medium group (Others or Water based (DC >= 4))
7. Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
8. Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
9. Setup → Level
Displays the measured level L (for verification purposes).
10. Setup → Distance
Displays the distance D between the reference point R and the level L (for
verification purposes).
11. Setup → Signal quality
Displays the signal quality of the analyzed level echo (for verification purposes).
12. Setup → Mapping  →  Confirm distance
Compare the distance displayed with the actual value in order to start recording an
interference echo map
2)
.
2) In the case of FMP54 with gas phase compensation (product structure: feature 540 "Application packages", option
EF or EG), mapping cannot be performed