Levelflex FMP51 Modbus Commissioning
Endress+Hauser 31
8.3.2 Configuring interface measurement
An interface measurement is only possible if the device has the corresponding software
option. In the product structure: feature 540 "Application Package", option EB "Interface
measurement".
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK (DC )
2 2
DK DC
1 1
( )
A0011177
 8 Configuration parameters for interface measurement
R = Reference point of measurement D
I
= Interface distance (distance from flange to DK
2
)
E = Empty calibration (= zero point) L
I
= Interface
F = Full calibration (= span) D
L
= Distance
LN = probe length L
L
= Level
UP = Measured thickness upper layer
1. Setup  →  Device tag
Enter device tag.
2. Setup  →  Distance unit
Select the length unit.
3.
Setup  →  Operating mode
3)
Select Interface option.
4. Setup  →  Tank type
Select tank type.
3) Only available in devices with the "Interface measurement" application package