Commissioning Levelflex FMP51 Modbus
32 Endress+Hauser
5. Setup  →  Tube diameter (only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
6. Setup  →  Tank level
Specify the filling level (Partially filled or Fully flooded)
7. Setup  →  Distance to upper connection
In bypasses: Specify the distance from the reference point R to the lower edge of the
upper outlet; in all other cases, keep the factory setting
8. Setup  →  DC value
Specify the dielectric constant of the upper medium
9. Setup  →  Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
10. Setup  →  Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
11. Setup  →  Level
Displays the measured level L
L
.
12. Setup  →  Interface
Displays the interface height L
I
.
13. Setup  →  Distance
Displays the distance D
L
between the reference point R and the level L
L
.
14. Setup  →  Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
15. Setup  →  Signal quality
Displays the signal quality of the analyzed level echo.
16. Setup  →  Mapping  →  Confirm distance
Compare the distance displayed with the actual value to start recording an
interference echo map.