Safety instructions:
Zone 0
In the event of potentially explosive vapor/air mixtures, only operate the device under atmospheric
conditions.
- Temperature: –20 to +60 °C
- Pressure: 80 to 110 kPA (0.8 to 1.1 bar)
- Air with normal oxygen content, usually 21 % (V/V)
Associated devices with galvanic isolation between the intrinsically safe and non-intrinsically safe circuits are
preferred.
If there is a risk of dangerous potential differences within Zone 0 (e.g. through the occurrence of atmospheric
electricity), implement suitable measures for intrinsically safe circuits in Zone 0 (e.g. in accordance with the
requirements of GB3836.13, GB3836.15, GB3836.16).
Temperature tables Èä19
Connection data Basic specification, Position 1, 2 (Approval) = N2
Ex ia
Power supply and signal circuit with protection type: intrinsic safety Ex ia IIC or IIB
Service interface (CDI)
Taking the following values into consideration, the device can be connected to the Endress+Hauser FXA291
service tool or a similar interface:
Basic specification, Position 3 (Power Supply; Output) = G TRC [06]
Terminal 1 (+), 2 (–) Terminal 3 (+), 4 (–)
FISCO: Entity: Ausgang PFS:
U
i
= 17.5 V
I
i
= 550 mA
P
i
= 5.5 W
U
i
= 30 V
I
i
300 mA
P
i
= 1.2 W
U
i
= 30 V
I
i
= 300 mA
P
i
= 1 W
U
o
= 0 V
effective inner inductance L
i
= 10 μH
effective inner capacitance C
i
= 5 nF
leak current 50 μA
effective inner inductance L
i
= 0 mH
effective inner capacitance C
i
= 24 nF
Service interface
U
i
= 7.3 V
effective inner inductance L
i
= negligible
effective inner capacitance C
i
= negligible
U
o
= 7.3 V
I
o
= 100 mA
P
o
= 160 mW
permitted outer inductance L
o
= negligible
permitted outer capacitance C
o
= negligible