EasyManua.ls Logo

Endress+Hauser Levelflex FMP55 HART - 7 Electrical Connection; Connection Conditions

Endress+Hauser Levelflex FMP55 HART
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP55 HART Electrical connection
Endress+Hauser 21
7 Electrical connection
7.1 Connection conditions
7.1.1 Terminal assignment
2-wire: 4-20mA HART
8
9
1
+
2
4...20mA
HART
10 mm
Spare part
71108xxx
2- wire level
4-20 mA 4-20 mA
HART
[21]
open
-
1
+
2
4-20mA
1-channel overvoltage protection
-
[16]
A
7
B
!
4...20 mA
5
4
1
2
3
+
+
#
+
4...20 mA
5
4
1
2
3
+
6
#
A0011294
 6 Terminal assignment 2-wire; 4-20mA HART
A Without integrated overvoltage protection
B With integrated overvoltage protection
1 Active barrier with power supply (e.g. RN221N): Observe terminal voltage
2 HART communication resistor (≥ 250 Ω): Observe maximum load
3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)

Other manuals for Endress+Hauser Levelflex FMP55 HART

Related product manuals