EasyManua.ls Logo

Endress+Hauser Levelflex FMP55 HART - Page 27

Endress+Hauser Levelflex FMP55 HART
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP55 HART Electrical connection
Endress+Hauser 27
4-wire: 4-20mA HART (10.4 to 48 V
DC
)
3
1
+
L+
4
2
4...20 mA
HART
10.4...48 V=
10 mm
Spare part
71108xxx
2- wire
4-20 mA
HART
[08]
open
-
L-
A
13
12
11
9
10
2
3
4
7
8
5
1
!
!
+
-
6
!
4...20 mA
≥250
A0011340
 9 Terminal assignment 4-wire; 4-20mA HART (10.4 to 48 V
DC
)
1 Evaluation unit, e.g. PLC
2 HART communication resistor (≥ 250 Ω): Observe maximum load
3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
4 Analog display device: Observe maximum load
5 Signal cable including screening (if required), observe cable specification
6 Protective connection; do not disconnect!
7 Protective earth, observe cable specification
8 4...20mA HART (active): Terminals 3 and 4
9 Supply voltage: Terminals 1 and 2
10 Supply voltage: Observe terminal voltage, observe cable specification
11 Terminal for potential equalization
12 Cable entry for signal line
13 Cable entry for power supply

Other manuals for Endress+Hauser Levelflex FMP55 HART

Related product manuals