EasyManua.ls Logo

Endress+Hauser Levelflex FMP57 - Page 171

Endress+Hauser Levelflex FMP57
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP56, FMP57 FOUNDATION Fieldbus Operating menu
Endress+Hauser 171
Selection Alarm
Alarm or warning
Warning
Factory setting Alarm
Switch-on value
Navigation  Setup → Advanced setup → Switch output → Switch-on value
Prerequisite Switch output function (→  169) = Limit
Description Enter measured value for the switch-on point.
User entry Signed floating-point number
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters:
Switch-on value > Switch-off value
The output is closed if the measured value is larger than Switch-on value.
The output is opened if the measured value is smaller than Switch-off value.
t
t
A
B
C
D
A0015585
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
Switch-on value < Switch-off value
The output is closed if the measured value is smaller than Switch-on value.
The output is opened if the measured value is larger than Switch-off value.

Table of Contents

Related product manuals