Levelflex FMP56, FMP57 FOUNDATION Fieldbus Operating menu
Endress+Hauser 137
17.3 "Setup" menu
: Marks the navigation path to the parameter via the display and operating
module.
: Marks the navigation path to the parameter via an operating tool (e.g.
FieldCare).
: Marks parameters which can be locked via the software locking →  58.
Navigation  Setup
Distance unit
Navigation  Setup → Distance unit
Description Select distance unit.
Selection SI units
mm
m
US units
ft
in
Factory setting m
Bin type
Navigation  Setup → Bin type
Prerequisite Medium type (→  148) = Solid
Description Specify bin type.
Selection Concrete
Plastic wood
Metallic
Aluminium
Factory setting Metallic
Empty calibration
Navigation  Setup → Empty calibr.
Description Specify the distance E between the process connection and the minimum level (0%). This
defines the starting point of the measuring range.
User entry Depending on the probe