Operating menu Levelflex FMP56, FMP57 FOUNDATION Fieldbus
148 Endress+Hauser
"Level" submenu
Navigation  Setup → Advanced setup → Level
Medium type
Navigation  Setup → Advanced setup → Level → Medium type
Description Specify type of medium.
User interface Liquid
Solid
Factory setting FMP56, FMP57: Solid
Additional information This parameter determines the value of several other parameters and strongly
influences the complete signal evaluation. Therefore, it is strongly recommended not
to change the factory setting.
Medium property
Navigation  Setup → Advanced setup → Level → Medium property
Prerequisite EOP level evaluationFix DC
Description Specify relative dielectric constant ε
r
of the medium.
Selection Unknown
DC 1.4 ... 1.6
DC 1.6 ... 1.9
DC 1.9 ... 2.5
DC 2.5 ... 4
DC 4 ... 7
DC 7 ... 15
DC > 15
Factory setting Dependent on Medium type (→  148) and Medium group.