Commissioning (block-based operation) Levelflex FMP56, FMP57 FOUNDATION Fieldbus
96 Endress+Hauser
Step Block Parameter Action
7 SETUP (TRDSUP) Signal quality
(signal_quality)
Displays the signal quality of the level echo.
8 SETUP (TRDSUP) Confirm distance
(confirm_distance)
Compare the displayed distance to the real
distance in order to start the recording of the
mapping curve.
Selection:
179: Manual map
32847: Delete all
32859: Distance ok
32860: Distance too big
32861: Distance too small
32862: Distance unknown
33100: Tank empty
12.6 Configuration of the on-site display
12.6.1 Factory settings of the on-site display for level measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Levele linearized Levele linearized
Value 2 display Distance Distance
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 21
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
12.7 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)
Functions of the parameter options
Options Description
33097: Execute backup A backup copy of the current device configuration in the HistoROM is saved to the
display module of the device. The backup copy comprises the transmitter data of
the device.
33057: Restore The last backup copy of the device configuration is copied from the display module
to the HistoROM of the device. The backup copy comprises the transmitter data of
the device.
33838: Duplicate The transmitter configuration from another device is duplicated to the device using
the display module.