Liquiphant S, Nivotester
10 Endress+Hauser
Installation Installation, wiring and commissioning
Installation, wiring and commissioning of the device is described in the Operating Instructions (→ ä 6,
"Supplementary device documentation").
SD175en04
* Overvoltage protector HAW560Z and HAW562Z if required
"
Caution!
Note the following for Nivotester FTL670:
The operator must use suitable measures (e.g. current limiter, fuse) to ensure the following characteristics for
the fail-safe contact and alarm relay are not exceeded:
•U ≤ 230 V AC, 50/60 Hz , I ≤ 2.5 A,
P ≤ 600 VA at cos ϕ = 1.0 or P ≤ 300 VA at cos ϕ ≥ 0.7 or
•U ≤ 120 V DC, I ≤ 2.5 A, P ≤ 75 W
"
Caution!
Changes to the measuring system and settings after start-up can impair the protection function!
Orientation
The permitted orientations of the device are described in the Operating Instruction (→ ä 6, "Supplementary
device documentation").