Micropilot FMR60/62/67
14 Endress+Hauser
10.
Setting
Set write protection = enter the locking code again (WHG: 7450; SIL: 7452; SIL and WHG:
7454). Check the locking status after performing SIL locking.
Navigate to: Setup → Advanced setup
Setting
Locking status = SIL locked must be confirmed by selecting "".
11.
As an option, hardware locking can also be activated (via the dip switch marked "WP" on the
main electronics).
Locking in "Expert mode"
To commission the device, carry out and document the following steps in the order shown
(→  30).
1.
Reset device. This resets all parameters to defined values.
Navigate to: Setup → Advanced setup → Administration
Setting
Device reset = To factory defaults or To delivery settings
2.
Carry out configuration. The configuration procedure and the meaning of the individual
parameters are described in the Operating Instructions (→  7). The following parameter
settings must be observed (→  15).
3.
Perform a device check (for more details, see the Operating Instructions →  7). The signal
quality is tested here and possible installation errors are detected.
Navigate to: Diagnostics → Device check
Setting
Start device check = Yes
4.
Start SIL/WHG confirmation sequence.
Navigate to: Setup → Advanced setup → SIL/WHG confirmation
Setting
Set write protection = enter the relevant locking code (HG: 7450; SIL: 7452; SIL and WHG:
7454).
5.
Setting
Commissioning = Expert mode
The device checks the parameter settings in accordance with the following table and forces
the switching of parameters if necessary.
When the check is finished, SIL/WHG preparation = Finished is shown. The commissioning
sequence can be continued. Press "Next" to confirm.
The commissioning mode must not be changed during the completion of the SIL
confirmation sequence. If the wrong option has been selected, the sequence must be
canceled and started again.
6.
Carry out function test.
For MIN and MAX monitoring, at least one level below (MIN monitoring) or above (MAX
monitoring) the switch point must be approached.
For range monitoring, 5 distance values should be approached which cover the entire
measuring range. Verify in each case that the response of the current output is correct.
7.
Confirm that the function test has been successful.
Setting
Confirm function test = Yes
8.
Setting
Set write protection = enter the locking code again (WHG: 7450; SIL: 7452; SIL and WHG:
7454). Check the locking status after performing SIL locking.
Navigate to: Setup → Advanced setup → Locking status
Setting
Locking status = SIL locked must be confirmed by selecting "".
9.
Optional, hardware locking may also be activated (via the dip switch marked "WP" on main
electronics).