Micropilot FMR60/62/67
Endress+Hauser 15
Further parameter settings
The following parameters affect the safety function. However, they may be freely configured in
accordance with the application. In increased safety mode, it is necessary to confirm the configured
values during the remainder of the commissioning process. Confirmation is not required in expert
mode.
It is recommended to note down the configured values!
Parameter Parameter name
Setup
Empty calibration
Full calibration
Tank type
1)
Bin type
2)
Max. filling speed solid
2)
Max. draining speed solid
2)
Medium group
Setup → Advanced setup → Level Tank/silo height
1) Only for liquid measurement
2) Only for bulk solids measurement
The following parameters affect the safety function and are not freely configurable in increased
safety mode. Instead, they are automatically changed by the device at the start of the SIL/WHG
confirmation to the safety-oriented values mentioned. If these parameters are to be set to other
values, expert mode must be selected.
Parameter Preset value
Setup → Advanced setup → Level → Level correction 0
Setup → Advanced setup → Linearization → Linearization type None
Setup → Advanced setup → Current output 1 → Damping output 0
Expert → Sensor → Level → Distance offset 0
Expert → Sensor → Level → L max. drain speed 0
Expert → Sensor → Level → L max. fill speed 0
Expert → Sensor → Level → Level limit mode Off
Expert → Sensor → Level → Output mode Ullage
Expert → Sensor → Safety settings → Jump delay echo lost Off
Expert → Sensor → Safety settings → Delay time echo lost 3 s
Expert → Sensor → Safety settings → Output echo lost Alarm
Expert → Sensor → Safety settings → In safety distance Alarm
Expert → Sensor → Echo tracking → Evaluation mode History off
Expert → Output → Current output 1 → Turn down Off
Expert → Output → Current output 1 → Measuring mode Standard
Expert → Communication → Configuration → HART address 0