Electrical connection Nivotester FTL325P, 3-channel
14 Endress+Hauser
6.2.2 Connecting the sensor
1 2
7
+
37
8
38
33 34
A0039153
 8 Connecting the sensor to the Nivotester
Connectable sensors:
Liquiphant FTL51B/62/64 with FEL67
Liquiphant M FTL50(H), FTL51(H), FTL51C with FEL57
Liquiphant S FTL70/71 with FEL57
Soliphant M FTM50, FTM51, FTM52 with FEM57
Blue terminal blocks at top for hazardous area
Twin-core connecting cable between the Nivotester and sensor, e. g. commercially
available instrument cable or cores in a multi-core cable for measurement purposes
Use a shielded cable in the event of increased electromagnetic interference, e. g. from
machines or radio equipment. Only connect the shield to the grounding terminal in the
sensor. Do not connect it to the Nivotester.
6.2.3 Connecting the signal and control systems
Gray terminal blocks at bottom for the non-hazardous area
Relay function depending on the level and safety mode
If a device with high inductance is connected (e. g. contactor, solenoid valve), a spark
arrestor must be installed to protect the relay contact .
6.2.4 Connecting the supply voltage
Green terminal block at bottom
A fuse is integrated into the power supply circuit. An additional fine-wire fuse is not
necessary. The Nivotester is equipped with reverse polarity protection.