Nivotester FTL325P, 3-channel Electrical connection
Endress+Hauser 13
6 Electrical connection
6.1 Connection conditions
L
WARNING
Risk of explosion due to faulty connection.
Observe applicable national standards.
Comply with the specifications in the Safety Instructions (XA).
Check to ensure that the power supply matches the information on the nameplate.
Switch off the supply voltage before connecting.
When connecting to the public mains, install a mains switch for the device such that it
is within easy reach of the device. Mark the power switch as a disconnector for the
device (IEC/EN61010).
6.2 Connecting the measuring device
The removable terminal blocks are color-coded into intrinsically safe and non-
intrinsically safe terminals. This difference helps to ensure safe wiring.
6.2.1 Arrangement of terminals
Observe the specifications on the nameplate of the device.
L1
L+
L1
N
L–
N
2 16
1 15
B
A
C
D
A0039151
 7 Arrangement of terminals
A U 85 to 253 V
AC
, 50/60 Hz
B U 20 to 30 V
AC
, 50/60 Hz
C U 20 to 60 V
DC
D Max. 1.5 mm² (max. AWG 16)