Prosonic M FOUNDATION Fieldbus Wiring
Endress+Hauser 17
3.6 Supply voltage
The following values are the voltages across the terminals directly at the instrument:
minimum terminal voltage: 9 V
maximum terminal voltage: 32 V
The current consumption is approx. 15 mA for the range of voltages given above.
3.7 Recommended connection
L00-FMU4xxxx-17-00-00-yy-014
1: external ground terminal of the transmitter
For maximum EMC protection please observe the following points:
As the metal housing of the Prosonic M is isolated from the tank by the plastic sensor, a
low-impedance connection between the housing and tank/bracket/flange should be installed
in order to ensure electromagnetic compatibility (EMC).
For optimum EMC the connection should be as short as possible. Ideally, a ground strap
should be used.
The continuity of the cable screening between tapping points must be ensured.
If potential equalisation is present between the individual grounding points, ground the
screening at each cable end or connect it to the device housing (as short as possible).
If there are large differences in potential between grounding points, the grounding should run
via a capacitor that is suitable for high frequency use (e.g. ceramic 10 nF/250 V&).
"
Caution!
Applications, which are subject to the explosion prevention, permit only under special
conditions the repeated grounding of the protective screen , see to EN 60 079-14.
1
1