RIA14
6 Endress+Hauser
Operability
Local operation
a0011157
LC display of the field indicator (illuminated, pluggable in 90° stages)
Item 1: bargraph display in increments of 10% with indicators for measuring range undershoot (item 1a)/overshoot (item 1b)
Item 2: measured value display, character height 20.5 mm (0.8")
Item 3: 14-segment display for units and information messages
Item 4: symbol "programming disabled"
Item 5: unit "%"
Item 6: warning symbol "failure"
•Display range
-19999 to +99999
•Offset
-19999 to +99999
Signalling
Measuring range overshoot/undershoot
Limit value violation
Lower/upper limit value exceeded
Operating elements
3-key operation (-/+/E) integrated in device, access with housing open
Remote operation Configuration
The device is configured with the FieldCare PC operating software. FieldCare Device Setup forms part
of the scope of supply of Commubox FXA291 or TXU10-AC (see ‘Accessories’) or can be downloaded
free of charge from the Internet at www.endress.com.
Interface
Configuration interface at device; connection to PC via configuration cable (see "Accessories").
Configurable device parameters (selection)
Measuring dimension, measuring ranges (linear/square), setup block using user code, failsafe mode,
digital filter (damping), offset, limit value (min/max/alarm), alarm limit values freely adjustable.