Cells and accessories are dispatched in wooden boxes. Electrolyte is dispatched in plastic drums which are approved for
marine transportation.
2. Delivery and storage
A moist charged battery is a wet, fully charged battery that has had the electrolyte removed and has a special, air-tight
plug used during storage.
1. Definition of moist charged batteries
Do not remove the special air-tight plugs from the moist charged batteries until ready to activate.
Moist-charged batteries are active and electrically live at all times.
Do not short terminal posts.
Accessories and tools required
Please ensure that all accessories and tools are available before starting the installation of the battery.
Sulphuric acid in plastic drum
Manual filler pump
Thermometer
Hydrometer
Funnel
Rigid connector + Caps Cable + Caps
Tool for air-tight plugs
Until ready for use, a moist-charged battery must be stored in a cool, dry and clean location, away from any source of heat
and protected from direct sunlight. In those conditions, moist charged cells can be stored for up to 2 years.