EasyManua.ls Logo

ENERVEX Multiple Fireplace - Control Settings; Choosing the Draft Set-Point; Checking Fan Rotation (3-Phase Only)

ENERVEX Multiple Fireplace
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
3940011 12.12
5.1 Control Settings
The control must be set to run in Continuous mode for this system. To do this, set dipswitch #1 to the On/Up
position. The dipswitch is located on the back of the display board inside the EBC 30 control box. See the
picture below.
5. START-UP AND CONFIGURATION
Control Settings for Negative Pressure Applications
Parameter Setting
21 Draft Set-point *To Be Determined at Start-Up
22 Exhaust Mode Continuous
262 Alarm Delay 30 Seconds
5.2 Choosing the Set-Point
Thedrafteffectsofthechimneyfanwilldecreaseasthereplacesbecomefurtherawayandthesetpointmust
besettoensureaconstant,negativepressureatthefurthestreplacefromthefan.Formostapplications,the
set-point will be between 0.05” W.C. and 0.10” W.C.
Topreventthereplaceslocatedclosetothefanfromover-drafting,adjustthestrokeoftheactuatoroneach
damper as described in Chapter 5.3.
5.3 Checking Fan Rotation (3-phase only)
Verify the fan blades are rotating clockwise. The EBC 30 can be set to run the fan at a very low
speed while doing this.
If the fan is rotating counter-clockwise, switch the phase wires connecting to terminals V and W of the VFD.