Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40 39 00-02-0939
2019-06-13
acknowledgement of the fault is NOT required to restart in Auto after shutdown occurs if
active shutdown is removed from controller)
Analog Inputs (1-3) (Medium Security): for each of the analog inputs, the ability to select the following
parameters exists:
Analog input 1 (Medium Security): Factory set to Function: Disabled
Analog Input 2 (Medium Security): Factory set to Function: Disabled
Analog Input 3 (Medium Security): Factory set to Function: Disabled
Function (Medium Security):
Disabled
4-20mA Suction Pressure
0-5V Suction Pressure
4-20mA Discharge Pressure
0-5V Discharge Pressure
4-20mA System Level
4-20mA Flow Rate
4-20mA Ambient Temp
0-5V Ambient Temp
4-20mA Gear Box Pressure
0-5V Gear Box Pressure
Datcon Oil Pressure
Murphy Oil Pressure (ES2P-100)
VDO5 Bar Oil Pressure
VDO7 Bar Oil Pressure
Murphy Engine Temp (ES2T-250/300)
Datcon Engine Temp
VDO Engine Temp
Murphy Fuel Level (ES2F)
VDO Fuel Level
Datcon Fuel Level
Murphy Oil Temp (ES2T-250/300)
Datcon Oil Temp
VDO Oil Temp
Murphy PMK-400 Pressure (Gear Box Pressure, Murphy PMK-400 Sensor)
Analog.Digital1
4-20mA Remote Throttle: (4mA = Min Engine Speed, 20mA = Max Engine Speed, Remote
Throttle Digital Input must be active to allow analog to work properly)
0.5-4.5V Remote Throttle: (0.5V = Min Engine Speed, 4.5V = Max Engine Speed, Remote
Throttle Digital Input must be active to allow analog to work properly)
Model 12 Air Temp Sensor: (Murphy 0-5V Model 12 preset Ambient Temp Sensor)
Sensor Setup (Medium Security): (This menu only appears when a transducer [4-20mA or 0-5V] is
selected for an analog input.)
Ambient Temp (0-5V) or (4-20mA)
Discharge Pressure (0-5V) or (4-20mA)
Suction Pressure (0-5V) or (4-20mA)
Flow Rate (4-20mA)
System Level (4-20mA)
Relay (1-3) and Digital (1-4) Outputs (Medium Security): these same parameters are used for both the
Relay and Digital Outputs.