2.1 Specications
Model 1KVAS-RT 1KVAH-RT 2KVAS-RT 2KVAH-RT 3KVAS-RT 3KVAH-RT
Rated Capacity 1KVA / 900W 2KVA / 1800W 3KVA / 2700W
Input
Rated input voltage
208Vac / 220Vac / 230Vac / 240Vac
Rated input frequency
50Hz / 60Hz (auto-sense)
Input voltage range
110 ~ 176Vac (power derating linearly between 50% and 100% load);
176 ~ 280Vac (no derating); 280 ~ 300Vac (power derating 50%)
Input frequency range
40 ~ 70Hz
PFC
≥ 0.99
THDI
≤ 6%
Bypass voltage range
-25% ~ +15% (settable)
Output
Output voltage 208Vac / 220Vac / 230Vac / 240Vac (settable)
Voltage accuracy ± 1%
Output PF 0.9
Inverter overload
capability
105% ~ 125% load: transfer to bypass in 1 min;
125% ~ 150% load: transfer to bypass in 30s;
> 150% load: transfer to bypass in 300 ms;
Load crest 3:1
From mains mode
to BAT mode
0 ms (transfer time)
From mains mode
to bypass
4 ms (typical)
Efciency
Line mode 90% 91% 92%
BAT mode 85% 86% 87%
ECO mode 95% 96% 97%