Input phases from grid or installation
one or three (depends on the
configuration)
Depends on the configuration, max.
44 kW
Depends on the configuration, max. 3 x
64 A
Number of charging spots (sockets)
Socket physical protection
Lid cover (optional locking when not in
use)
Charging coupler protection
Socket locking mechanism during
charging
Charging socket max. output power
(current)
Depends on the configuration; max
22 kW (3 x 32 A)
Simple shutdown for maintenance
fuse switch disconnector on input
Overcurrent protection of each socket
Additional thermal/logical protection
of the socket, based on deviations from
PWM setting
* I/Ipwm >105 % during T>1000s
* I/Ipwm>110 % during T>100s
* I/Ipwm>120 % during T>10s
Standby energy consumption
Depends on the configuration: max.
20 W with network switch and GPRS
modem installed
Differential protection of the socket –
RCD (ground leakage current)
Type A or Type B 30 mA compliant with
IEC 61008
Embedded smart energy meters
Disconnecting all phases and neutral
line
Monitors voltage on the socket level to
detect contactor welding or other
power supply faults
Overvoltage protection of the station
(optional)
Station can be equipped with Type B2
if connected to the electricity
distribution network; Type C if
connected to an existing installation.
Overcurrent protection of the
overvoltage protection (optional)
EVSE standards compliance
IEC 61851-1 – supports Mode 3
charging
ISO/IEC 14443A and ISO/IEC 15693
Mifare® Classic 1K (1KByte), Mifare®