Eubank EAA/EGA Wall Mount AC Installation & Operation Manual
03/2021 Rev.5
Chapter 8 Start-Up Check List
8.1 Start-Up & Commissioning Form
Please complete the information on this form and return to Marvair by mail or fax. The mailing address
and fax number can be found at the end of the form.
A. Equipment Information
Date: ________________Equipment Owner _______________________________________
Installing Company: _____________________________Installer: ____________________
Address: _______________________________________State _______________________
City: __________________________________________
ICE Air conditioner: Model No. _____________________________________________
Serial No. _____________________________________________
Compressor: Model No. _____________________________________________
Serial No. _____________________________________________
Compressor: Model No. _____________________________________________
Serial No. _____________________________________________
B. Pre-Start Up
Is there any shipping damage? Yes No
If so, where? ________________________________________________________________
Will this damage prevent starting the unit? Yes No
Check Power Supply, does it agree with data sticker on air conditioner? Yes No
Has the ground wire been connected? Yes No
Has the circuit protection been sized and installed properly? Yes No
Controls
Are the thermostat control wiring connections made and checked? Yes No
Are all wiring terminals (including main power supply) tight? Yes No
If unit has a crankcase heater, has it been energized for 24 hours? Yes No
On a 208/230 v. units is control transformer (24 AC) wired for correct voltage? Yes No
Condensate Section
Has water been placed in drain pan to conrm proper drainage? Yes No
Are correct lters in place? Yes No
Refrigerant Piping
If leaks are found, report any leaks to Marvair Warranty Service Dept.