1.4 Air Flow, Weights and Filter Sizes
Complete electrical and performance specications and dimensional drawings are in the Eubank Wall
Mount Air Conditioner Product Data Sheets.
Note: Follow local codes and standards when designing duct runs to deliver the required airow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
MODEL 0.10 0.15 0.20 0.25 0.30 0.40 0.50
EAA1020 800 785 770 725 680 600
EAA1024 800 785 770 725 680 600 500
EAA1030 1200 1150 1100 1050 1000 900 800
EAA1036 1290 1230 1170 111 5 1060 1000 920
EAA1042 1500 1430 1360 1295 1230 1160 1070
EAA1060 1900 1850 1800 1700 1600 1500 1350
EGA1072 1900 1850 1800 1700 1600 1500 1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage different from the rating point
will affect air flow.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
EAA1020/1024 30 x 16 x 2 762 x 406 x 52 80138 1 8
EAA1030/1036/1042 36½ x 22 x 2 927 x 559 x 52 80162 1 8
EAA1048/1060 18 x 24 x 2 457 x 610 x 52 81257 2 8
EGA1072 18 x 30 x 2 457 x 762 x 52 93184 2 8
Table 2. Return Air Filter Sizes
MODEL LBS KG
Non-Economizer
EAA1020/1024 355 160
EAA1030/1036/1042 535 245
EAA1048/1060 625 284
EGA1072
680 309
With Economizer
EAA1020/1024
375 170
EAA1030/1036/1042 590 268
EAA1048/1060 640 291
EGA1072 740 336
Table 3. Shipping Weights for Eubank Wall Mount AC Units
1.5 General Operation
Model Ventilation Conguration Temperature Range
Non-Economizer
Standard ("N") 20ºF – 120ºF (-7ºC – 48.9ºC)
Desert Duty ("ND") 32ºF – 130ºF (-0ºC – 54ºC)
Extreme Duty ("NE"), 60 Hz Only 0ºF – 130ºF (-18ºC – 54ºC)
With Economizer
Standard ("CE") -40ºF – 120ºF (-40ºC – 48.9ºC)
Desert Duty ("CD") -40ºF – 130ºF (-40ºC – 54ºC)
Extreme Duty ("CE"), 60 Hz Only -40ºF – 130ºF (-40ºC – 54ºC)
Table 4. Ambient Temperature Operating Range
Model
EAA1018A EAA1020A EAA1024A EAA1030A EAA1036A EAA1042A EAA1048A EAA1060A EGA1072A
A A A C D Z A C D Z A C D Z A C D Z A C D Z A C D Z A C D Z
w/o Hot Gas Reheat 65 85 85 90 105 123 128 125 150 160
w/Hot Gas Reheat N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Table 5. Refrigerant Charge (R410A, Ounces)