Label Visibility default min max UM description
S16 U
Temperature regulation mode
0: Cold
1: Hot
2: Auto+Cold
3: Auto+Hot
S17 S 0 2
Heating/Cooling mode setting
0: Cold
1: Hot
2: Auto
S18 U °C-°F Changeover probe value
S19 U
°C-°F Room probe value
S20 U
°C-°F External probe value
S21 U
°C-°F Return air humidity probe value
STem Temperature regulation
S22 U -10.0 100.0 °C-°F Temperature setpoint
S23 S
Temperature regulation type
0: Disabled
1: Follow-on regulation
2: Regulation on room temperature
3: Regulation on supply temperature
4: Forced by DI
S24 S °C-°F Regulation probe
S25 S °C-°F Temperature setpoint in use
S26 S
First coil type
0: Not available
1: Thermodynamic
2: 3-point, water
3: Modulating, water
4: ON-OFF, water
5: 2-step, electric
6: Modulating, electric
7: ON-OFF, electric
255: Not configured
S27 S
2nd coil type
0: Not available
1: ---
2: 3-point, water
3: Modulating, water
4: ON-OFF, water
5: 2-step, electric
6: Modulating, electric
7: ON-OFF, electric
255: Not configured
S28 S
Thermodynamic coil operating mode
0: OFF
1: ON
S29 S
Water coil 1 operating mode
0: OFF
1: ON
S30 S % Coil 1 valve opening
S31 S
Water coil 2 operating mode
0: OFF
1: ON
S32 S % Coil 2 valve opening