EVCO S.p.A.
EV3 HRV & EVD HRV | Application manual ver. 1.0a | Code 1443DHRVE104
page 68 of 74
The maximum lengths of the connection cables are as follows:
- power supply: 10 m (32.8 ft)
- analogue inputs: 10 m (32.8 ft)
- power supply for transducer analogue inputs 4-20 mA: 10 m (32.8 ft)
- digital inputs: 10 m (32.8 ft)
- analogue outputs 0-10 V: 10 m (32.8 ft)
- phase cutting analogue outputs: 10 m (32.8 ft)
- PWM analogue outputs: 1 m (3.28 ft)
- digital outputs: 10 m (32.8 ft)
- INTRABUS ports: 10 m (32.8 ft)
- RS-485 MODBUS ports: 1,000 m (3,280 ft); see also the MODBUS manual "specifications and
implementation guides" available on http://www.MODBUS.org/specs.php.
- USB port, 1 m (3.28 ft)
Use cables of an adequate section for the current running through them.
For EV3 HRV cabling we recommend using the CJAV39 connection kit (to be ordered separately). For
EVD HRV cabling instead, we recommend using the CJAV38 connection kit (to be ordered
separately).
Operating temperature:
EV3 HRV from -10 to 55 °C (from 14 to 131 °F)
EVD HRV
from -10 to 55 °C (from 14 to 131 °F)
EV3K11 from 0 to 55 °C (from 32 to 131 °F)
EVJ LCD from 0 to 40 °C (from 32 to 104 °F)
Storage temperature:
EV3 HRV
from -20 to 70 °C (from -4 to 158 °F)
EVD HRV
EV3K11
EVJ LCD
Operating humidity:
EV3 HRV
Relative humidity without condensate from 10 to 90% EVD HRV
EV3K11
EVJ LCD Relative humidity without condensate from 5 to 95%
Pollution status of the
control device:
EV3 HRV
2
EVD HRV
EV3K11
EVJ LCD
Compliance:
EV3 HRV - RoHS 2011/65/EC
- WEEE 2012/19/EU
- REACH (EC) Regulation no. 1907/2006
- EN 60730-1
- IEC 60730-1
- R&TTE 1999/5/EC (only applicable for EVJ LCD)
EVD HRV
EV3K11
EVJ LCD
Power supply:
EV3 HRV
12 VAC (+10 -15%), 50/60 Hz (±3 Hz), max. 7 VA not insulated
Protect the power supply with a 1 A-T 250 V fuse
EVD HRV
115... 230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 6 VA insulated
Protect the power supply with a 2 A-T 250 V fuse
EV3K11
- 12 VAC (±15%), 50/60 Hz (±3 Hz), max. 5 VA not insulated
- 12 VDC (±15%), max. 5 W not insulated
Protect the power supply with a 1 A-T 250 V fuse