Evco S.p.A. EVF815 | Installer manual ver. 1.1 | Code 144F815E114
page 30 of 58
P0 0 1 - - - - 0
probe type
0 = PTC
1 = NTC
P1 0 1 - - - - 1
°C decimal point
1 = yes
P2 0 1 - - - - 0
temperature unit of measurement (2)
0 = °C
1 = °F
P3 0 1 - - - - 1
enabling the needle probe
1 = yes
P4 0 1 - - - - 1
enabling the evaporator probe
1 = yes
P8 0 250 ds 5
delay displaying temperature variation detected by the
probes
P9 0 2 - - - - 1
type of backlight
0 = off during “on” status and during the “run” status
and with START/STOP key low light intensity during
the “stand-by” status
1 = with low light intensity during the “on” status and
during the "run" status and with START/STOP key
low light intensity during the “stand-by” status
2 = with high light intensity during the “on” status and
during the "run" status and with START/STOP key
high light intensity during the “stand-by” status
Par. Min. Max. Unit Default Main regulator
r0 0.1 15.0 °C/°F (1) 2.0 parameters differential r7, r8, r9, r10, r11 and r12
r1 1 500 min 90 duration of time-controlled blast chilling
r2 1 500 min 240 duration of time-controlled deep freezing
r3 -99.0 99.0 °C/°F (1) 3.0
temperature-controlled blast chilling end time temperature;
also end temperature of the temperature-controlled soft
deep freezing phase (temperature detected by the needle
probe); see also parameter r5
r4 -99.0 99.0 °C/°F (1) -18.0
temperature-controlled deep freezing end temperature
(temperature detected by the needle probe); see also
parameter r6