C850 25 532015 - Rev.B
Translation of the original instructions
ENGLISH
Display Funzione Impostazione
13
When this function is activated, the CLOSE command during opening stops operation,
otherwise the CLOSE command commands immediate reverse or when opening is
completed (see also parameter
14)
Y = CLOSE stops
no = CLOSE reverses
14
When this function is activated and if the parameter 13 is “no”, the CLOSE command
commands immediate closing at the end of the opening cycle (stores CLOSE). If the
parameters
13 and 14 are “no”, CLOSE commands immediate closing.
Y = closes at the end of opening
no = inmediate closure
15
When this function is activated, with the system stopped by a STOP another OPEN
command moves in the opposite direction. If the parameter
15 is “no”, it always closes.
Y = moves in the opposite direction
no = always closes
16
When this function is activated, during closing, the CLOSING SAFETY DEVICES stop and
allow motion to resume when they are no longer engaged, otherwise they immediately
reverse opening.
Y = closes when no longer engaged
no = immediate reversal
17
When this function is activated, the CLOSING SAFETY DEVICES command closing when
they are no longer engaged
(see also parameter 18).
Y = closes when FSW is no longer
engaged
no = disabled
18
When this function is activated and if the parameter 17 is Y, the unit will wait for the opening
cycle to end before executing the closing command sent by the CLOSING SAFETY
DEVICES.
Y = closes at the end of opening
no = disabled
19
When this function is activated, during closing, LOOP2 stops and allows motion to resume
when no longer engaged, otherwise it immediately reverses to opening.
Y = closes when no longer engaged
no = immediate reversal
20
When this function is activated, LOOP2 commands closing when it is no longer engaged
(see also parameter
21).
Y = closes if LOOP2 is clear
no = disabled
21
When this function is activated and if the parameter 20 is Y, the unit will wait for the
opening cycle to end before executing the closing command sent by LOOP2.
Y = closes at the end of opening
no = disabled
22
When this function is activated, the LOOP1 commands have priority over those of LOOP2.
Y = active
no = disabled
23
LOOP 1 commands opening and, once completed, it closes if no longer engaged (useful
in case of vehicle back-up with consecutive loops). If disabled, when LOOP 1 is no longer
engaged, it does not close.
Y = closes if LOOP1 is clear
no = disabled
24
NOT USED /
25
A.D.M.A.P Function
When this function is activated, the result is operation of safety devices compliant with
French standards.
Y = active
no = disabled
26
When this function is activated, the CLOSING SAFETY DEVICES during closing stop and
reverse movement when they are no longer engaged, otherwise they reverse immediately.
Y = stops and reverses when no
longer engaged.
no= reverses immediately
27
NO EFFECT /
A1
PRE-FLASHING:
Lets you adjust, in 1 sec steps, the desired duration of pre-fl ashing, from a minimum of 00 to
a maximum of 10 seconds
05
A2
TIMEOUT FOR REVERSE WHEN CLOSING:
If this function is activated, during closing you can decide to reverse or stop movement when
the timeout elapses (the closing limit switch is not reached).
Y = reverses
no = stops
A3
OPENING AT POWER UP:
In the event of a power failure, once it is restored, you can command opening by enabling
this function (only if the automated system is not closed, FCC clear).
Y = opens
no = remains stationary
St
AUTOMATED SYSTEM STATUS:
Exit programming, store settings and return to gate status display (see paragraph 11.5.1.).
11.8.1. PERSONALISING THE OPERATING LOGIC
The expert programming level values vary depending on the operating logic chosen at the basic programming level.
The expert programming level is for personalising one of the selectable logics should a non-standard operating mode be required.
To make effective the change of one or more expert programming level parameters that personalise the set operating logic, proceed
as follows:
Select the basic logic that most suits your needs.
Enter the expert programming level and change the desired parameters.
Exit expert level from the basic level and select the logic
Cu.
The logic
Cu activates the changes made at expert level.