E045 22 732786 - Rev.C
ENGLISH
Display Advanced Function
Default
PF
PRE-FLASHING:
You can enable/disable the pre-flashing. Pre-flashing duration = 3 sec.
Y = enabled before each movement
no = disabled
no
EC
ANTI-CRUSHING SENSITIVITY (visualised only with the function En
=
Y):
Varying this function varies the amount of time after which, in case of obsta-
cle, the board commands reversal of the leaves, or it will command a stop
if the leaves are in the contact point search space (see the parameter
rB).
The fourth consecutive obstacle detected in the same direction and position
will be defined as a contact point and the leaf will stop in that position.
00 = minimum sensitivity (maximum time before reversal)
10 = maximum sensitivity (minimum time before reversal)
05
r8
CONTACT POINT SEARCH ANGLE (visualised only with the function En = Y):
You can adjust the contact point search angle within which the board will stop
movement without reversing, if it encounters an obstacle or the contact point.
Adjustable in two modes:
01 = Low contact point search space (about 1 degree)
02 = High contact point search space (about 4 degree)
02
tA
ADDITIONAL OPERATING TIME (displayed only if function En = no):
You can add a work time at the end of movement.
Adjustable from 0 to 30 sec in 1 sec steps.
This time is not considered when calculating the deceleration per-
centage.
03