13400 Owner’s Manual
P/N 446613 Issue I Rev. A I-7
Power limited
Maximum Standby Current: 1.0 mA
Alarm Voltage: 24 VDC nominal
Maximum Alarm Current: 1.5 A
Maximum Ripple: 15 VAC
Maximum Loop Drop Voltage: 1.0 VDC
Status Relays (alarm and trouble)
For connection to Power limited sources only
Contact Rating: 2A, 30 VDC maximum, resistive
0.5, 30 VAC maximum, resistive
City Tie (Option)
Reverse Polarity
Power limited
Voltage: 24 VDC nominal
Alarm Tie Current: 0.010 amp maximum
Trouble Tie Current: .010 amp maximum
Ripple: 1 VAC maximum
Local Energy
Non-Power limited
Voltage: 24 VDC nominal
Standby Current: 0.014 amp. maximum
Alarm Current: 0.51 amp maximum
Ripple: 1 VAC maximum
Maximum wire loop resistance: 30
Trip coil impedance: 14.5 ohms
Remote LED Annunciator Driver Circuit (Option)
Power limited
Voltage: 24 VDC nominal
Maximum Current: 80mA.
Maximum wire loop resistance: 100ohms
Alarm Zone Relays (Option)
For connection to Power limited sources only
Contact Rating: 2A, 30 VDC maximum, resistive
0.5 A, 30 VAC maximum, resistive