Section I Descriptions
I-6 P/N 446613 Issue I Rev. A
General Specifications
The 13400 is a small, processor-controlled fire alarm control unit incorporating most
commonly used features as standard or add-on equipment.
Environmental
Operating temperature
Normal: 68-77° F (20 - 25° C)
Extreme: 32 - 120° F (0 - 49° C) up to 3 hours
Relative humidity
Extreme: 85% @ 86° F up to 24 hours
Primary Input Voltage
Primary Input Voltage:
13400-120 120 VAC (50/60 Hz) nominal
13400-240 240 VAC (50/60 Hz) nominal
Maximum primary input current:
13400-120 1.00 A at 120 VAC
13400-240 .5 A at 240 VAC
Secondary and Trouble Power Supply
24 volt lead-acid battery set:
Maximum Charge Voltage: 28 VDC
Maximum Charge Current: 1 A
Maximum Input Current: 3A
Battery capacity: 7-17.2 AH
Power Outputs
Current: 200 milliamp maximum (Total of all resettable (R) and non-resettable (NR)
power outputs - annunciator power, four-wire smoke power and auxiliary
relay board power)
.5 amp Auxiliary Power Output (must be subtracted from NAC power)
Non-Resettable Power Outputs (NR+, NR-)
Power limited
Voltage: 24 VDC nominal
Current: 200mA max.
Ripple: 1 VAC maximum
Resettable Power Output (R+,R-)
Power limited
Voltage: 24 VDC nominal
Current: 200mA max.
Ripple: 1 VAC maximum
Auxiliary Power Output (AUX+, AUX-)
Power limited
Voltage: 24 VDC nominal
Current: 500mA max.
Ripple: 15 VAC maximum
Initiating Device Circuits
Power limited
Four Class B, Style B zones minimum
Standby voltage range: 16-27 VDC
Maximum standby current: 10 mA.
Maximum standby detector current: 3.0 mA @ 24 VDC
Maximum alarm current: 66 mA
Maximum ripple: 1 VAC
Maximum wire loop resistance: 100 ohms
Notification Appliance Circuits