Section II Operation Instructions
II-2 P/N 446613 Issue I Rev. A
Trouble Operation
A trouble is indicated by the following conditions:
! The yellow System Trouble LED flashes.
! The trouble buzzer sounds a slow pulsating tone.
! The yellow Zone Trouble LED flashes
! If a remote station type of city connection is used, a trouble signal is sent to the
remote station.
! The trouble relay will also activate to serve various functions.
To silence the trouble buzzer:
! Momentarily press the Trouble Silence button.
! The yellow System Trouble LED stops flashing and lights steady indicating the
condition was silenced.
! If the trouble condition has been restored, the system may return to the normal
standby condition. The system may need to be reset to restore the system to a
normal standby condition.
! Notify the proper personnel for servicing the system immediately.
! Refer to Appendix B, Troubleshooting Guide.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not
to initiate a fire alarm sequence.
Sprinkler Supervisory Operation
(This applies only to control panels that have been configured for sprinkler supervisory
switches.)
A supervisory is indicated by the following conditions:
! The yellow System Supervisory LED flashes.
! The buzzer sounds a pulsating tone.
! The yellow Zone Trouble LED flashes using a longer pulse rate than that of the
trouble condition.
! If a remote station type of city connection is used, a trouble signal is sent to the
remote station.
To silence the supervisory tone:
! Momentarily press the Trouble Silence button.
! Locate the activated switch and return it to its normal position.
! If a supervisory condition still exists, notify the proper personnel for servicing the
system immediately.