13400 Owner’s Manual
P/N 446613 Issue I Rev. A I-1
Section I : Descriptions
This section provides an overview of the 13400, including the following:
! Introduction
! Minimum control unit configuration
! Optional control unit configurations
! Optional Devices
! General operating parameters
! General Specifications
Introduction
The 13400 is a conventional, modular fire alarm control unit with the following standard
features and options:
Control Unit Features
! 4 Class B (Style B) Initiating Device Circuits (IDC).
! 2 Class B (Style Y) Notification Appliance Circuits (NAC).
! 2.25 amps of Notification Appliance Power.
! 200ma of resettable and/or non-resettable power.
! .5 amps unfiltered Auxiliary Power (subtracted from NAC Power)
! General alarm operation.
! Dry contact status relay outputs, form-C, rated 2.0A at 30VDC / 0.5A at 30 VAC,
resistive, (alarm and trouble).
! Operates one supervised remote LED annunciator.
! Battery charger with no and low battery supervision.
! Push button switches for: system reset, trouble silence, alarm silence, lamp test,
city tie disable, zone/sig disable, general alarm, and history recall.
! Ground fault detection, positive and negative.
! Dual level IDC operation for waterflow (zone 4 only) and supervisory devices.
! Automatic NAC short circuit disconnect circuitry.
Settings for
! Alarm verification selectable for each IDC.
! Manual alarm silence with 0, or 1 minute inhibit.
! Steady output pattern selectable by NAC to be silenceable or non-silenceable.
! “Quick Test” by system.
! Silent or audible “Quick Test”.
Expansions and Options
! Alarm Relay Board providing a form “C”, 2.0 A at 30 VDC or 0.5 A at 30 VAC,
resistive, fire alarm contact from each initiating device circuit and additional alarm
and trouble contacts.
! Semi-flush mounting trim ring.
! Remote LED Annunciator Driver with zone alarm outputs.
! City Tie with Local Energy/Remote Station connections