MAINTENANCE
070002_3_B
FGP 50/2 EVO-2
15
The control-box stops the burner
with fuel spraying but no flame (red light
on).
1) The ignition circuit is broken. 1) Check the circuit completely.
2) The ignition transformer cables have dri-
ed over time.
2) Replace them.
3) The ignition transformer cables are not
well connected.
3) Fasten them.
4) The ignition transformer is cut off. 4) Replace it.
5) The electrode faces are not at the right
distance.
5) Adjust them to the prescribed position.
6) Electrodes discharge to earth since they
are dirty or with a cracked insulation;
also check under the clamps fastening the
insulating materials.
6) Clean or, if necessary, replace them.
TYPE OF IRREGULARITY PROBABLE CAUSE RIMEDY