TECHNICAL CHARACTERISTICS
070002_3_B
FGP 50/2 EVO-2
2
TECHNICAL CHARACTERISTICS
TECHNICAL DATA FGP 50/2 EVO-2
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
*** For burner FGP 50/2 EVO-2 with long head add 1 kg to the weight.
OPERATING RANGE DIAGRAM FGP 50/2 EVO-2
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
MODEL
FGP 50/2 EVO-2
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 9.9/20-53.1
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 100.1/204-541.8
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 117.4/237-630
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 1.1
Fan motor [kW] 0.74
Nominal motor current absorption [A] 1.8
Nominal auxiliary absorption [A] 0.3
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness ** min-max [dBA] 71-73
Burner weight *** [kg] 31
Fig. 1 X = Thermal power Y = Pression in the combustion chamber
0
2
4
6
8
10
12
0 200 400 500 600 700
[kW]
[mbar]
100 300