1.0 System Overview
1.1 Description
The FCI 7100 is a multiprocessor-based analog/addressable fire alarm control panel, designed for commer-
cial, industrial and institutional fire alarm applications. It is available with one or two signaling line circuits.
The 7100 Series Fire Alarm Control is Listed by Underwriters Laboratories Standard UL 864. It is suitable for
the following signaling services:
• Automatic Fire Detector alarm
• Manual Fire Alarm
• Waterflow Alarm
• Supervisory
• Automatic smoke alarm, non-coded and master coded operation
• Releasing Device service
The 7100 Series complies with the requirements of the following National Fire Protection Association (NFPA)
Standards:
• NFPA 13 - Installation of Sprinkler Systems
• NFPA 16 - Deluge Foam-Water Sprinkler Systems
• NFPA 16A - Installation of Closed Head Foam-water Sprinkler Systems
• NFPA 72 - National Fire Alarm Code:
– Central Station Fire Alarm Systems
– Local Fire Alarm Systems
– Auxiliary Fire Alarm Systems
– Remote Station Fire Alarm Systems
– Proprietary Fire Alarm Systems
1.2 Features
1.2.1 Standard Features
• Two (2) Class B, Style 4 Signaling Line Circuits - Model 7100-2/D (One circuit in Model 7100-1/D)
• Two (2) Class B, Style Y Notification Appliance Circuits
• Alarm and Trouble dry contacts
• Accommodates 99 FCI Approved, UL Listed compatible analog sensors per SLC
• Accommodates 98 FCI Approved, UL Listed compatible addressable monitor/control devices per SLC
• 80-character alphanumeric LCD display
• 500 event history buffer (non-volatile)
• Power limited
• Resettable/Non-resettable 1.0 amp. @ 24 VDC power output
• Alarm verification
• Walk test
• Multi-level alarm processing
• Positive alarm Sequence (PAS) operation
• NAC coding
• Trouble reminder
• Integral RS-232 port
• Key Switch - keyed alike with the door lock and renders the key pad inoperative until activated.
1.2.2 Optional Features
• Class A Module (CAOM) with Disconnect Switches for NACs and SLCs
• Digital Alarm Communicator (DACT) (Model 7100-D)
• RS-232 Printer Transient Module (PTRM), Supervised
• Municipal Circuit Option Module (MCOM)