EasyManuals Logo

FCI 7100 SERIES User Manual

FCI 7100 SERIES
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
3.1 Power
3.1.1 AC Input
Connection of the 120/240 VAC, 50/60 Hz power source must be made per the requirements of the National
Electrical Code, NFPA 70, Article 760, the applicable NFPA requirements, and/or the Authority Having
Jurisdiction.
Guidelines to follow are:
Connections must be to a dedicated branch circuit
Connections must be mechanically protected
All means of disconnecting the circuit must be clearly marked: “FIRE ALARM CIRCUIT CONTROL.
Accessible only to authorized personnel.
For 240 VAC operation, no conductor shall have a potential greater than 150 V to ground.
See Table 1 for AC input and battery connections.
3.1.2 Battery Connections
TB7-1 is positive. See Table 1.
TB7-2 is negative. See Table 1.
Observe polarity
See Table 2 for Battery Calculations
3.1.3 Auxiliary Power Output, Resettable/non-resettable
TB4-1 Resettable, 24 VDC, max. 1.0 amp. Suitable for use with projected beam smoke detectors SPB-24,
770 Series, or DH Series duct detectors.
TB4-2 Non-resettable, 24 VDC, max. 1.0 amp. Suitable for use with the FM Series door holders.
NOTE: Total output is 1.0 amp max. combined.
TB4-3 Common negative
TB4-4 Not used
3.1.4 Earth Ground Connection
TB4-4 Earth Ground
3.2 Relay Connections
System Trouble Contacts
TB2-1 Normally Open
TB2-2 Common
TB2-3 Normally Closed
Transfers on any trouble condition and/or supervisory alarm.
System Alarm Contacts
TB2-4 Normally Open
TB2-5 Common
TB2-6 Normally Closed
Transfers upon any system alarm except supervisory.
Designation Description Comments
LEDs
LED25 Yellow Line 1 Trouble
LED26 Yellow Line 2 Trouble
Jumpers
W1 Not used
W2 OUT to disable battery
W3 IN - No Local Phone Line 1
W4 IN - No Local Phone Line 2
J6 Connection to keypad
JMP1 Cut for 240 VAC input operation
Table 1a - LEDs, Jumpers
IMPORTANT: Always apply AC power first, then connect the batteries.
14 of 43 9000-0447
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the FCI 7100 SERIES and is the answer not in the manual?

FCI 7100 SERIES Specifications

General IconGeneral
Series7100 SERIES
ManufacturerFCI
Sensor TypePhotoelectric
Operating Temperature Range32°F to 120°F (0°C to 49°C)
TypeSmoke Alarm
Operating Temperature32°F to 120°F (0°C to 49°C)
Alarm Sound Level85dB at 10 feet
Interconnect CapabilityYes
Dimensions2 inches
Humidity10% to 95% non-condensing
Humidity Range10% to 95% non-condensing