TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS
Recovered heating capacity Desuperheater unit (VD)
MOD.
TWR
OUTDOOR AIR TEMPERATURE (°C D.B.)
25 30 35
40
45
kWt
r
=
RECOVERED HEATING CAPACITY [KW]
50
30
12.4 14.2 16.3 18.6 21.2
35
12.4 14.2 16.4 18.7 21.3
40
12.2 13.9 16.0 18.3 20.8
45
11.5 13.2 15.2 17.4 19.8
50
10.6 12.1 13.9 15.9 18.1
55
9.3 10.6 12.2 14.0 15.9
60
7.6 8.8 10.1 11.5 13.1
65
5.7 6.5 7.5 8.5 9.7
70
3.3 3.8 4.4 5.0 5.7
60
30
13.9 15.9 18.2 20.8 23.6
35
14.0 16.0 18.3 20.9 23.8
40
13.7 15.7 17.9 20.4 23.2
45
13.0 14.9 17.0 19.4 22.1
50
11.9 13.7 16.4 17.8 20.2
55
10.4 12.0 14.4 15.6 17.7
60
8.6 9.9 11.9 12.9 14.6
65
6.4 7.3 8.8 9.5 10.8
70
3.8 4.3 5.2 5.6 6.4
70
30
15.9 18.2 20.8 23.7 27.0
35
15.9 18.3 20.9 23.9 27.1
40
15.6 17.9 20.4 23.3 26.5
45
14.8 17.0 19.4 22.2 25.2
50
13.6 15.6 17.8 20.3 23.1
55
11.9 13.7 15.6 17.8 20.3
60
9.8 11.3 12.9 14.7 16.7
65
7.3 8.3 9.5 10.9 12.4
70
4.3 4.9 5.6 6.4 7.3
80
30
18.7 21.5 24.6 28.2 32.0
35
18.8 21.6 24.7 28.3 32.2
40
18.3 21.1 24.2 27.6 31.4
45
17.4 20.0 22.9 26.2 29.8
50
15.9 18.3 21.0 24.0 27.3
55
13.9 16.0 18.4 21.0 23.9
60
11.4 13.2 15.1 17.2 19.6
65
8.4 9.7 11.1 12.7 14.5
70
4.9 5.7 6.5 7.4 8.4
90
30
21.7 24.8 28.2 32.3 36.7
35
21.8 24.9 28.3 32.4 36.8
40
21.2 24.3 27.6 31.6 36.0
45
20.1 23.0 26.2 30.0 34.1
50
18.4 21.1 24.0 27.4 31.2
55
16.1 18.5 21.0 24.0 27.3
60
13.2 15.2 17.2 19.7 22.4
65
9.8 11.2 12.7 14.5 16.5
70
5.7 6.5 7.4 8.5 9.6
100
30
24.4 27.8 31.5 35.8 40.5
35
24.5 27.9 31.6 35.9 40.6
40
23.9 27.2 30.8 35.0 39.6
45
22.6 25.7 29.2 33.2 37.5
50
20.7 23.5 26.7 30.3 34.3
55
18.1 20.6 23.3 26.5 30.0
60
14.8 16.8 19.1 21.7 24.5
65
10.8 12.3 14.0 15.9 18.0
70
6.2 7.0 8.0 9.1 10.3
MOD.
TWR
OUTDOOR AIR TEMPERATURE (°C D.B.)
25 30 35
40
45
kWt
r
=
RECOVERED HEATING CAPACITY [KW]
115
30
27.8 31.6 35.9 40.6 45.8
35
27.8 31.6 35.9 40.6 45.8
40
27.1 30.8 35.0 39.6 44.7
45
25.7 29.3 33.2 37.6 42.5
50
23.7 26.9 30.5 34.6 39.1
55
20.9 23.8 27.0 30.6 34.5
60
17.5 19.9 22.6 25.6 28.9
65
13.4 15.2 17.3 19.6 22.1
70
8.6 9.8 11.1 12.6 14.2
130
30
31.2 35.3 40.1 45.4 51.4
35
31.2 35.3 40.1 45.4 51.4
40
30.4 34.5 39.1 44.3 50.1
45
28.9 32.7 37.1 42.0 47.5
50
26.5 30.0 34.1 38.6 43.7
55
23.4 26.5 30.1 34.1 38.5
60
19.5 22.1 25.1 28.4 32.1
65
14.8 16.8 19.1 21.6 24.4
70
9.4 10.6 12.0 13.6 15.4
145
30
35.7 40.6 46.0 52.1 58.8
35
35.7 40.5 45.9 52.0 58.7
40
34.7 39.5 44.7 50.6 57.2
45
33.0 37.4 42.4 48.1 54.3
50
30.3 34.5 39.0 44.2 49.9
55
26.9 30.5 34.6 39.2 44.2
60
22.5 25.6 29.0 32.9 37.1
65
17.4 19.7 22.3 25.3 28.6
70
11.3 12.9 14.6 16.5 18.7
160
30
39.8 45.2 51.2 58.0 65.5
35
39.9 45.3 51.4 58.2 65.7
40
39.0 44.3 50.1 56.8 64.2
45
36.9 41.9 47.5 53.8 60.8
50
33.8 38.3 43.4 49.2 55.6
55
29.5 33.5 38.0 43.0 48.6
60
24.2 27.4 31.1 35.2 39.7
65
17.7 20.1 22.8 25.8 29.1
70
10.1 11.5 13.0 14.8 16.7
180
30
43.9 49.8 56.5 64.0 72.2
35
44.1 50.0 56.7 64.2 72.5
40
43.0 48.8 55.3 62.7 70.8
45
40.7 46.3 52.4 59.4 67.0
50
37.3 42.3 47.9 54.3 61.3
55
32.6 37.0 41.9 47.5 53.6
60
26.6 30.3 34.3 38.8 43.8
65
19.5 22.2 25.1 28.5 32.1
70
11.2 12.7 14.4 16.3 18.4
200
30
48.7 55.3 62.6 70.9 80.1
35
48.8 55.5 62.8 71.2 80.4
40
47.7 54.1 61.3 69.5 78.5
45
45.2 51.3 58.1 65.8 74.3
50
41.3 46.9 53.1 60.2 68.0
55
36.1 41.0 46.4 52.6 59.4
60
29.5 33.5 38.0 43.1 48.6
65
21.6 24.6 27.8 31.5 35.6
70
12.4 14.1 15.9 18.1 20.4
kWtr = RECOVERED HEATING CAPACITY [KW]
TWR = Desuperheater outlet water temperature, Δtin-out= 5°C