EasyManua.ls Logo

Ferroli VTP 15 - Wall Unit Installations; Air Vent; Condensate Drain

Ferroli VTP 15
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
INSTALLATION
WALL UNIT INSTALLATIONS
AIR VENT
CONDENSATE DRAIN
Fig 1
Fig 3
Fig 4
INGRESSO ACQUA
USCITA ACQUA
ISOLAMENTO
NO
INGRESSO ACQUA
USCITA ACQUA
ISOLAMENTO
INGRESSO ACQUA
USCITA ACQUA
NO
1 The insulation must cover both water inlet and outlet pipes as shown
2 Use polyethylene insulation (minimum thickness 8mm)
1 Connect the water inlet and outlet pipes, turn the unit on and set it
to cool mode; make sure the valve opens
In this way water starts entering the coil
2 Check for water leaks along the hydraulic connections
If there are no leaks, open the air vent and air starts coming out of
the coil
Attention: During these operations, be careful not to touch live
electrical parts
3 Close the air vent
Carry out the condensate drain pipe connection, making sure nothing
can hinder the natural drainage of the condensate which forms in
cooling mode
Proceed as follows:
Ensure a minimum slope for the flow of condensate
Avoid any hindrances to the flow
After connecting, make sure the water flows properly out of the
machine
1 Connect the condensate drain pipe
2 Make sure the drain pipe does not have traps or curves that hinder
the flow of condensate
3 Check correct flow by pouring water into the tray and make sure it
comes out through the drain pipe installed
Fig 2
WATER INLET WATER INLET WATER INLETWATER OUTLET
INSULATION
INSULATION
WATER OUTLET WATER OUTLET

Related product manuals