Note: Only test each zone after the panel is free of faults and has no active events. Only
the enabled zones are selected for the test mode.
Selecting the zone to be tested
To select the zone to be tested, use the Left Navigation or Right Navigation buttons.
The selected zone fault LED and test LED flash in sync.
Applying the test mode to the selected zone
To activate the test condition on the selected zone, activate a detector or a manual call point.
When the detector or call point is active, the zone fault LED, test LED, and the respective fire
alarm LED flash in sync with each other until the sounder turns on and off the selected zone
number of times. For example, if zone 3 is selected for test mode, the sounder turns on and off
three times.
Note: Restore the call point if it is used to test a zone. Otherwise, it continues to run the
test on the respective zone.
Exiting the zone test selection mode
Press the Function button when the test is completed or to exit test mode.
The test LED and selected zone fault LED turn off.