Access levels
There are four access levels in the Essential Panel:
Access level 1
Entry
- Level 1 is the default access level for users.
- The accessed LED remains off in access level 1.
Functionality
- All users can view the panel status.
- Additionally, the internal buzzer silence, lamp test and override delay features are available.
Exit
- Level 1 is the default access level for users.
Access level 2
Entry
- To enter access level 2, insert the enable key and rotate it to position 1.
- The accessed LED flashes continuously to indicate that the panel is in access level 2.
Functionality
- All functions applicable at access level 1 are available at level 2.
- Additionally, sounder silence/resound, reset of the system, manual evacuation, enable/
disable of delays for zones, enable/disable of zones and sounders, and test mode features
are available.
Exit
- To exit access level 2, turn the enable key switch to position 0 and remove the key.
- The accessed LED turns off to indicate that the panel is in the default access level.
Access level 3
Entry
- Ensure that the enable key is removed from the panel.
- To enter access level 3, use the appropriate tools to open the front door of the panel.
- Press the Enable/Disable button, Left Navigation button, Right Ravigation button, and
3rd Level Access button in sequence.
-
Note: The time taken between button presses must not exceed 10 seconds.
- The accessed LED turns steady on, to indicate that the panel is in access level 3.
Note: If the button sequence is not completed in 10 seconds, then the buzzer beeps to
indicate a login timeout.
Functionality
- Only qualified users with authorized access are allowed to enter this level.
- All functions applicable at access levels 1 and 2 are applicable at this level.
- Set delay to output time in minutes for all zones.
Exit
- Press the 3rd Level Access button to exit access level 3.
- The accessed LED turns off.
- Close the front door and insert the screws into the designated areas.
7FireClass Essential Panels User Manual