Enable and disable
The following section contains information about the enabling or disabling of zones and sounders.
Entering enable or disable programming
1. Enter access level 2.
2. Press the Function button twice, to select the programming mode.
The enable/disable LED turns steady on.
3. To select a zone or sounder, press the Right Navigation button.
The zone 1 fault LED flashes in sync with the enable/disable LED if the zone is enabled, or is
steady on if the zone is disabled.
Selecting a zone or sounder
To select a zone or sounder for enabling or disabling, use the Left Navigation or Right
Navigation buttons.
Enabling/disabling the zone or sounder
Before you begin:
See Entering enable or disable programming and Selecting a zone or sounder.
Press the Enable/Disable button.
The selected zone or sounder fault LED either flash in sync with the enabled/disabled LED or
turn steady on, depending on the state:
- Flashing zone or sounder fault LED - enabled
- Steady on zone or sounder fault LED - disabled
Exiting the enable/disable mode
Press the Function button to save the enable/disable status of respective zones or sounders.
The enabled/disabled LED turns on or off depending on the enable/disable status.
- If any of the zones or sounders are disabled, the enabled/disabled LED turns steady on.
- If all of the zones and sounders are enabled, the enabled/disabled LED turns off.
Note: A disabled output is prevented from operating under any circumstances.
Important: When a zone is disabled, power is still supplied to the zone, but alarms and
faults are prevented from triggering in that zone. If devices in disabled zones are activated
for any reason, their LEDs light up as power is supplied to those zones.
Zone test condition
The following section contains information about the zone test condition.
Accessing test selection mode
1. Log on to access level 2.
2. Press the Function button.
The test LED turns steady on in program selection mode.
3. Press the Right Navigation button to enter test mode.
The test LED and zone fault LED flash in sync.
13FireClass Essential Panels User Manual