13
Adding text and zone information without
software
Complete the following steps to add text and zone
information without software:
1. Press the 1 key to select the Program option
on the MAIN screen.
2. Enter the installer password and press
ENTER. Each digit will be masked by an
asterisk. The default installer password is
00000.
3. Press the 2 key to select Device.
4. Select the loop by using the Right and Left
cursor keys and press ENTER.
5. Select the device by using the Right and Left
cursor keys and press ENTER.
6. The control panel will prompt you to indicate if
you want to remove the device. Use the Right
and Left cursor keys to select NO and press
ENTER.
7. Use the alphanumeric keypad to enter the
required text in the dedicated field. Use the
cursor key Up to change the text to capitals
and the cursor key Down to change the text to
lower case. Use the 0 key to add a space.
Press ENTER to confirm the text. Press
ENTER again if you do not want to change the
WORKING MODE until the zone number is
highlighted.
8. Use the alphanumeric keypad, to enter the
required zone number and press the ENTER
key to confirm.
9. If a change of the device base is not required,
press the ENTER key. The control panel
resets.
Repeat steps 1-8 for all of the addresses you want to
edit.
Testing and monitoring the devices
Check that each device activates correctly. Use the
one man test facility or complete a live test. Examples
of testing include testing call points by pressing the
Activate key or testing smoke detectors with a smoke
aerosol can.
If the auto-addressing procedure was followed, some
devices will already have been verified.
Testing the local and loop sounders
1. Press the EVACUATE key on the panel to
issue an alarm. Check that the sounder has
operated.
2. After the test, press the SILENCE/RESOUND
key and then press the RESET key.
Note: Be aware of the possible nuisance caused
by the alarms and take any required measures.
Testing the open sounder circuit monitoring
1. Disconnect any EOL resistors or associated
circuits in the system. Ensure that the control
panel reports the appropriate faults.
2. After the test, restore the system to normal.
Testing the short sounder circuit monitoring
1. Replace any EOL resistors or associated
circuits in the system with a short circuit.
Ensure that the control panel reports the
appropriate faults.
2. After the test, restore the system to normal.
WALK TEST procedure
1. Press the 1 key to select the Program option
on the MAIN screen.
2. Enter the installer password and then press
ENTER. Each digit will be masked by an
asterisk. The default installer password is
00000.
3. Use the 3 key to select the SW Zone screen.
4. Select the number zone and press ENTER.
5. Use the Right and Left cursor keys to select
an option. The keys have the following
functions:
OFF: does not perform the procedure.
ALL: selects all the devices assigned to zones
in WALK TEST mode. It will not generate an
alarm in the case of their activation but will
reach the TEST status.
DET: selects only the detectors assigned to
zones in WALK TEST mode. It will not
generate an alarm in the case of their
activation but will reach the TEST status.
CP: selects only the call-points assigned to
zones in WALK TEST mode. It will not
generate alarm in the case of their activation
but will reach the TEST status.
6. Press the ENTER key to confirm the selection.
The presence of a zone in WALK TEST mode is
signaled by the TEST yellow LED on the user
interface. More than one zone can be put in WALK
TEST mode at the same time.