10
Fig. 10-3 Clearance 'B' Diagram
Combustible
Min.
18"
(Clearance required for
right, left, and rear)
Fig. 10-2 Clearance 'A' Diagram
Non-combustible
Min.
4"
(Clearance required for
right, left, and rear)
Installation must be performed by a qualifi ed professional service
technician.
This grill is designed for outdoor use only. DO NOT use this grill inside
a building, garage, enclosed area, or under overhead combustible
construction.
See below and the EXHAUST REMOVAL section on the following
page for details on installing under non-combustible overhead
construction.
DO NOT use this grill in or on a recreational vehicle or boat.
Important: This grill is not insulated. Refer to the information
below to ensure all required clearances are met.
The grill must have a minimum clearance of 18" from combustible
materials/items AT ALL TIMES.
OVERHEAD CONSTRUCTION REQUIREMENTS
(IF APPLICABLE)
This outdoor cooking gas appliance shall not be used under
overhead combustible construction.
A minimum clearance of 5 feet is required between the countertop
and the construction above (Fig. 10-1).
SIDE AND REAR WALL CLEARANCES
For the minimum clearances between the grill and any side or rear
walls, your setup must fall within one (or more) of the following:
A. Clearance between grill and strictly non-combustible wall
(i.e. brick wall, see Fig. 10-2)
The grill must have a minimum of 4" right, left, and rear
clearance from any non-combustible wall.
(To allow for proper ventilation and prevent dangerous
overheating.)
B. Clearance between grill and combustible wall
The grill must have a minimum of 18" right, left, and rear
clearance from any combustible wall (see Fig. 10-4).
Fig. 10-1 Overhead requirements
Min.
5'
INSTALLATION REQUIREMENTS
NON-COMBUSTIBLE
CONSTRUCTION ONLY
REV 1 - 1603020805
L-C2-436