The high gas pressure switch has opened and the control is waiting until
the condition corrects itself.
2
(Terminal 27)
HOLD MESSAGES
1
2
DESCRIPTION
The high temperature switch has opened and the control is waiting until
the condition corrects itself. (Terminal 32).
The high pressure switch has opened and the control is waiting until the
condition corrects itself.
2
(Terminal 31).
The high water cutoff circuit has opened and the control is in a hold con-
dition until it close.
2
(Terminal 23). *
The low atomizing media switch has opened and the control is waiting until
the condition corrects itself.
3
(Terminal 30)
The low gas pressure switch has opened and the control is waiting until the
condition corrects itself.
2
(Terminal 30)
The low oil pressure switch has opened and the control is waiting until the
condition corrects itself.
2
(Terminal 28)
The low oil temperature switch has opened and the control is waiting until
the condition corrects itself.
2
(Terminal 29)
The low water cutoff circuit has opened and the control is waiting until the
condition corrects itself.
2
(Terminal 24)
The fuel selection switch was opened during, or at the beginning of an
operating cycle.
2
(Terminal 25 or 26)
1.
Messages more than 16 characters in length will scroll from right to left on the bottom line of the display.
2.
HOLD messages only apply to recycle-type programmers i.e. EP260 or EP380, EP390 set for recycle operation.
3.
This condition will hold for 10 minutes on an EP260, EP270, EP380, EP390 series programmer before a lockout will occur.
HOLD PURGE
3-P HIGH GAS PRESSURE
HOLD PURGE
3-P HIGH TEMPERATURE
HOLD PURGE
3-P HIGH PRESSURE
HOLD PURGE
3-P LOW ATOMIZING MEDIA
HOLD PURGE
3-P LOW GAS PRESSURE
HOLD PURGE
3-P LOW OIL PRESSURE
HOLD PURGE
3-P LOW OIL TEMPERATURE
HOLD PURGE
3-P FUEL SELECTED